# Voltage drop calculator: single-phase and 3-phase, with the formula

Source: https://journeylisto.com/voltage-drop-calculator/ · Updated 2026-10-23

Free calculator · reviewed October 23, 2026

**Single-phase: VD = 2 × K × I × L ÷ CM. Three-phase: VD = 1.732 × K × I × L ÷ CM.** L is the one-way length in feet. Enter your numbers and the calculator gives the voltage drop, the percent and the steps.

## The calculator

Interactive tool on this page: The calculator (https://journeylisto.com/voltage-drop-calculator/#calculadora)

## Key facts

|  |  |
|---|---|
| Single-phase | VD = 2 × K × I × L ÷ CM |
| Three-phase | VD = 1.732 × K × I × L ÷ CM |
| K | 12.9 for copper and 21.2 for aluminum (at 75 °C). If a question gives K, use that. |
| CM | The conductor's circular mils, from NEC Chapter 9, Table 8. |
| Percent | VD ÷ source voltage × 100 |

Source: [IAEI, Voltage Drop Calculations](https://iaeimagazine.org/electrical-fundamentals/voltage-drop-calculations/) and [EC&M, Code Calculations](https://www.ecmweb.com/content/article/20891042/code-calculations) (K), and our calculation engine, checked by automated tests (the same one as the diagnostic).

## The voltage drop formula, letter by letter

- **VD**: the voltage drop, in volts.
- **2** (single-phase): counts both conductors, out and back. **1.732** (√3) is for three-phase.
- **K**: the resistance of a conductor 1 circular mil in area and 1 foot long (ohm × CM ÷ ft). Copper 12.9, aluminum 21.2.
- **I**: the load current, in amperes.
- **L**: the one-way length from the source to the load, in feet. Don't double it: the 2 does that.
- **CM**: the conductor's area in circular mils.

## Worked example: single-phase

A 120 V single-phase circuit with 12 AWG copper conductors (6,530 CM) carries 20 A to a load 150 ft away. K = 12.9. Voltage drop: **11.85 V** (9.88% of 120 V).

1. Single-phase voltage drop: VD = 2 × K × I × L ÷ CM.
2. VD = 2 × 12.9 × 20 × 150 ÷ 6,530 = 77,400 ÷ 6,530 = 11.85 V.
3. Percent = 11.853 V ÷ 120 V × 100 = 9.88%.
4. The 2 already counts both conductors (out and back), so use the one-way length and do not double it again.

## Worked example: three-phase

A 208 V three-phase circuit with 4/0 AWG copper conductors (211,600 CM) carries 147 A to a load 370 ft away. K = 12.9. Voltage drop: **5.74 V** (2.76% of 208 V).

1. Three-phase voltage drop: VD = 1.732 × K × I × L ÷ CM.
2. VD = 1.732 × 12.9 × 147 × 370 ÷ 211,600 = 1,215,224.89 ÷ 211,600 = 5.74 V.
3. Percent = 5.743 V ÷ 208 V × 100 = 2.76%.
4. Three-phase uses 1.732 (√3) in place of the single-phase 2.

## How the exam asks it

- On the exam, conductors are copper unless the question says otherwise.
- Our questions give the one-way length and the K value. If a question doesn't give K, use 12.9 for copper or 21.2 for aluminum.
- Check whether it asks for volts or for a percent of the source voltage.
- Common mistakes: forgetting the 2, using 1.732 on single-phase, or doubling the length.

More worked problems, with the minimum wire size and the maximum length: [Voltage drop: worked problems](https://journeylisto.com/blog/voltage-drop-practice-problems/).

## 3 practice questions

### Question 1

A 240 V single-phase circuit uses 8 AWG copper conductors (16,510 circular mils). It carries 36 A to a load 300 ft away (one-way length). Using K = 12.9, what percent of the 240 V source voltage is lost to voltage drop?

1. A 7.03%
2. B 3.52%
3. C 14.06%
4. D 6.09%

### See the step-by-step solution

**Correct choice: A, 7.03%**

1. Single-phase voltage drop: VD = 2 × K × I × L ÷ CM.
2. VD = 2 × 12.9 × 36 × 300 ÷ 16,510 = 278,640 ÷ 16,510 = 16.877 V.
3. Percent = 16.877 V ÷ 240 V × 100 = 7.03%.
4. The 2 already counts both conductors (out and back), so use the one-way length and do not double it again.
5. Small rounding differences are normal; pick the closest choice.

### Question 2

A 120 V single-phase circuit uses 8 AWG copper conductors (16,510 circular mils). It carries 26 A to a load 270 ft away (one-way length). Using K = 12.9, what is the voltage drop in volts?

1. A 9.50 V
2. B 21.94 V
3. C 5.49 V
4. D 10.97 V

### See the step-by-step solution

**Correct choice: D, 10.97 V**

1. Single-phase voltage drop: VD = 2 × K × I × L ÷ CM.
2. VD = 2 × 12.9 × 26 × 270 ÷ 16,510 = 181,116 ÷ 16,510 = 10.97 V.
3. The 2 already counts both conductors (out and back), so use the one-way length and do not double it again.

### Question 3

A 480 V three-phase circuit uses 1/0 AWG copper conductors (105,600 circular mils). It carries 116 A to a load 240 ft away (one-way length). Using K = 12.9 and 1.732 for √3, what is the voltage drop in volts?

1. A 5.89 V
2. B 6.80 V
3. C 10.20 V
4. D 3.40 V

### See the step-by-step solution

**Correct choice: A, 5.89 V**

1. Three-phase voltage drop: VD = 1.732 × K × I × L ÷ CM.
2. VD = 1.732 × 12.9 × 116 × 240 ÷ 105,600 = 622,023.55 ÷ 105,600 = 5.89 V.
3. Three-phase uses 1.732 (√3) in place of the single-phase 2.

## Find your missing points before exam day

12 calculations plus 4 quick questions, about 15–20 minutes, with step-by-step solutions in English or Spanish. No sign-up.

[Take the free diagnostic](https://journeylisto.com/#diagnostic)

Want to practice everything now? [Try 7 days free](https://journeylisto.com/#offer).

Free for 7 days. Then $39 a month until you cancel. We email you 2 days before. Cancel before and you pay nothing.

## Frequently asked questions

### What is the voltage drop formula?

Single-phase: VD = 2 × K × I × L ÷ CM. Three-phase: VD = 1.732 × K × I × L ÷ CM. L is the one-way length in feet and CM is the conductor’s circular mils.

### What K value do I use for copper and aluminum?

12.9 for copper and 21.2 for aluminum (at 75 °C). If a question gives you K, use that value.

### How do I calculate the voltage drop percent?

Divide the voltage drop by the source voltage and multiply by 100. For example, 11.85 V on a 120 V circuit is 9.88%.

### Do I double the length on a single-phase circuit?

No. Use the one-way length from the source to the load: the 2 in the single-phase formula already counts both conductors, out and back.

### Where do the circular mils come from?

From NEC Chapter 9, Table 8. For example, a 12 AWG conductor is 6,530 circular mils.

## Sources

- [IAEI: Voltage Drop Calculations (K = 12.9 copper, 21.2 aluminum, from Table 8 at 75 °C)](https://iaeimagazine.org/electrical-fundamentals/voltage-drop-calculations/)
- [EC&M: Code Calculations (K = 12.9 copper, 21.2 aluminum, at 75 °C)](https://www.ecmweb.com/content/article/20891042/code-calculations)
- [NFPA: NFPA 70, National Electrical Code, 2026 edition (Chapter 9, Table 8)](https://www.nfpa.org/product/nfpa-70-national-electrical-code-nec/p0070code)
- [PSI: Candidate Information Bulletin (updated 9/15/2026), pp. 13 and 14 (copper unless stated)](https://test-takers.psiexams.com/api/content/bulletin/1682)

Reviewed October 23, 2026. Published by Brian De Souza, co-founder of JourneyListo. TDLR, PSI and NFPA are the authorities. This is a summary in our own words: check the source before you act on it.

## Start

Free practice test: 12 calculations in about 15–20 minutes, step by step in English or Spanish. No sign-up, and your results right away.

Start the free diagnostic: https://journeylisto.com/start/