# Texas journeyman exam practice questions, with step-by-step solutions

Source: https://journeylisto.com/texas-journeyman-practice-questions/ · Updated 2026-10-23

Free guide · reviewed October 23, 2026

Here are **12 calculation questions** like the ones on the calculations portion of the PSI exam, with step-by-step solutions. They come from the same generator as our free diagnostic, on the 2026 NEC.

## Key facts

|  |  |
|---|---|
| Calculations portion | 26 questions in 110 minutes; 24 are scored. |
| To pass | 70%: 17 of 24. |
| First-time average | 13.15 of 24 on the calculations part. |
| Question rules | Copper unless stated. No exceptions or optional methods unless the question asks. |

Source: PSI bulletin ([English](https://test-takers.psiexams.com/api/content/bulletin/1682), pp. 8 and 12 to 14) and [TDLR staff report, May 12, 2026](https://www.tdlr.texas.gov/electricians/agendas/2026-05-12-elc-staff-reports.pdf).

## How to use them

- Work them with your exam calculator before you look at the solution.
- When you finish one, open “See the step-by-step solution”.
- The table values you need are given in each question. On the real exam you look them up in your 2026 NEC.
- Missing a formula? Use the [formula sheet](https://journeylisto.com/journeyman-formula-sheet/).

## The questions

### Question 1

A 2,500 W, 240 V single-phase baseboard heater is a resistive load (power factor 1.0). How much current does it draw?

1. A 6.01 A
2. B 13.02 A
3. C 10.42 A
4. D 18.04 A

### See the step-by-step solution

**Correct choice: C, 10.42 A**

1. Single-phase current: I = P ÷ V.
2. I = 2,500 W ÷ 240 V = 10.42 A.
3. No 1.732 here: that is only for three-phase. And 125% is for sizing conductors and breakers, not for the current the load draws.

### Question 2

A three-phase, 480 V load uses 50 kW of real power at a power factor of 0.95. What is the line current? (Use 1.732 for √3.)

1. A 63.3 A
2. B 60.1 A
3. C 109.6 A
4. D 57.1 A

### See the step-by-step solution

**Correct choice: A, 63.3 A**

1. Three-phase current: I = P ÷ (1.732 × V × PF).
2. P = 50 kW = 50,000 W.
3. 1.732 × 480 V × 0.95 = 789.792.
4. I = 50,000 ÷ 789.792 = 63.3 A.
5. kW is real power, so divide by the power factor as well.

### Question 3

A 120 V single-phase circuit uses 8 AWG copper conductors (16,510 circular mils). It carries 33 A to a load 210 ft away (one-way length). Using K = 12.9, what is the voltage drop in volts?

1. A 10.83 V
2. B 21.66 V
3. C 5.41 V
4. D 9.38 V

### See the step-by-step solution

**Correct choice: A, 10.83 V**

1. Single-phase voltage drop: VD = 2 × K × I × L ÷ CM.
2. VD = 2 × 12.9 × 33 × 210 ÷ 16,510 = 178,794 ÷ 16,510 = 10.83 V.
3. The 2 already counts both conductors (out and back), so use the one-way length and do not double it again.

### Question 4

A 208 V three-phase circuit uses 2/0 AWG copper conductors (133,100 circular mils). It carries 124 A to a load 290 ft away (one-way length). Using K = 12.9 and 1.732 for √3, what is the voltage drop in volts?

1. A 6.04 V
2. B 10.46 V
3. C 6.97 V
4. D 3.49 V

### See the step-by-step solution

**Correct choice: A, 6.04 V**

1. Three-phase voltage drop: VD = 1.732 × K × I × L ÷ CM.
2. VD = 1.732 × 12.9 × 124 × 290 ÷ 133,100 = 803,447.09 ÷ 133,100 = 6.04 V.
3. Three-phase uses 1.732 (√3) in place of the single-phase 2.

### Question 5

A box will contain 8 × 14 AWG insulated conductors (all spliced or terminated in the box), 1 receptacle connected to 14 AWG conductors, and 4 × 14 AWG equipment grounding conductors. There are no internal clamps, fittings or studs. The volume allowance for 14 AWG is 2.00 in³. What is the minimum box volume?

1. A 22.00 in³
2. B 24.75 in³
3. C 20.00 in³
4. D 28.00 in³

### See the step-by-step solution

**Correct choice: A, 22.00 in³**

1. Count allowances (each one = 2.00 in³ for 14 AWG).
2. Insulated conductors: 8 × 1 = 8.
3. 1 device: 1 × 2 = 2.
4. Equipment grounding conductors, all together: 1.
5. Total: 8 + 2 + 1 = 11 allowances × 2.00 in³ = 22.00 in³.
6. A device yoke counts 2. All the grounds together count just 1 (up to 4 of them).

### Question 6

A box will contain 5 × 14 AWG and 3 × 12 AWG insulated conductors (all spliced or terminated in the box), 1 switch connected to 12 AWG conductors, and these equipment grounding conductors: 1 × 12 AWG and 2 × 14 AWG. There are no internal clamps, fittings or studs. Volume allowances: 14 AWG = 2.00 in³, 12 AWG = 2.25 in³. What is the minimum box volume?

1. A 21.25 in³
2. B 27.50 in³
3. C 23.50 in³
4. D 24.75 in³

### See the step-by-step solution

**Correct choice: C, 23.50 in³**

1. 14 AWG conductors: 5 × 2.00 = 10.00 in³.
2. 12 AWG conductors: 3 × 2.25 = 6.75 in³.
3. Device: 2 × 2.25 in³ (based on the largest conductor connected to it, 12 AWG) = 4.50 in³.
4. Equipment grounding conductors: one allowance for the largest one (12 AWG) = 2.25 in³.
5. Minimum volume: 10.00 + 6.75 + 4.50 + 2.25 = 23.50 in³.

### Question 7

A branch circuit supplies 36 A of continuous load and 14 A of noncontinuous load. The breaker is a standard one (not listed for 100% continuous operation). What is the minimum standard rating for the overcurrent protective device?

1. A 60 A
2. B 50 A
3. C 70 A
4. D 80 A

### See the step-by-step solution

**Correct choice: A, 60 A**

1. Minimum rating = 125% of the continuous load + 100% of the noncontinuous load.
2. 1.25 × 36 A = 45 A; 45 A + 14 A = 59 A.
3. 59 A is not a standard size, so go up to the next standard size: 60 A.
4. Continuous means the maximum current runs for 3 hours or more.
5. In the 2026 NEC the 125% stays for sizing breakers and conductors. It is no longer added inside the Article 120 load calculation.

### Question 8

A feeder supplies 68 A of continuous load and 79 A of noncontinuous load. The breaker is a standard one (not listed for 100% continuous operation). What is the minimum standard rating for the overcurrent protective device?

1. A 175 A
2. B 225 A
3. C 200 A
4. D 150 A

### See the step-by-step solution

**Correct choice: A, 175 A**

1. Minimum rating = 125% of the continuous load + 100% of the noncontinuous load.
2. 1.25 × 68 A = 85 A; 85 A + 79 A = 164 A.
3. 164 A is not a standard size, so go up to the next standard size: 175 A.
4. Continuous means the maximum current runs for 3 hours or more.
5. In the 2026 NEC the 125% stays for sizing breakers and conductors. It is no longer added inside the Article 120 load calculation.

### Question 9

A single three-phase motor in continuous duty has a full-load current (FLC) of 42 A. Use this FLC as given (no table lookup needed). What is the minimum ampacity of its branch-circuit conductors?

1. A 52.50 A
2. B 42.00 A
3. C 105.00 A
4. D 72.74 A

### See the step-by-step solution

**Correct choice: A, 52.50 A**

1. Branch-circuit conductors for one motor: at least 125% of the full-load current.
2. 1.25 × 42 A = 52.50 A.
3. Bigger percentages like 175% or 250% belong to the motor’s short-circuit and ground-fault protection, which is a different step.

### Question 10

A 50 kVA single-phase transformer has a 277 V primary and a 120/240 V secondary. What is its full-load secondary current?

1. A 120.3 A
2. B 180.5 A
3. C 416.7 A
4. D 208.3 A

### See the step-by-step solution

**Correct choice: D, 208.3 A**

1. Single-phase transformer current: I = kVA × 1,000 ÷ V.
2. Use the full secondary voltage: 240 V (not 120 V).
3. I = 50 × 1,000 ÷ 240 = 50,000 ÷ 240 = 208.3 A.

### Question 11

Standard method (2026 NEC), single-family dwelling of 1,500 ft². Find the demand load for general lighting plus the 2 small-appliance circuits and 1 laundry circuit. Use 2 VA per ft², 1,500 VA per circuit, and these demand factors: first 3,000 VA at 100%, the rest (up to 120,000 VA) at 35%.

1. A 4,575 VA
2. B 7,500 VA
3. C 5,100 VA
4. D 3,000 VA

### See the step-by-step solution

**Correct choice: A, 4,575 VA**

1. General lighting (2026 NEC, 120.41): 1,500 ft² × 2 VA = 3,000 VA.
2. Small-appliance circuits: 2 × 1,500 VA = 3,000 VA. Laundry: 1,500 VA (120.52(A) and (B)).
3. Total before demand: 3,000 + 3,000 + 1,500 = 7,500 VA.
4. First 3,000 VA at 100% = 3,000 VA (Table 120.45).
5. Remaining 4,500 VA × 35% = 1,575 VA.
6. Demand load = 3,000 + 1,575 = 4,575 VA.
7. Watch out: 3 VA per ft² is the old unit load. In the 2026 NEC it is only used to count the general-purpose (lighting and receptacle) branch circuits (120.13), not in this calculation.
8. Add the small-appliance and laundry loads before applying the demand factors.

### Question 12

A 2,500 ft² single-family dwelling, standard method (2026 NEC): general lighting at 2 VA per ft² plus 2 small-appliance circuits and 1 laundry circuit at 1,500 VA each, with demand factors applied (first 3,000 VA at 100%, the rest at 35%). What is that demand load in amperes on a 120/240 V single-phase service?

1. A 22.0 A
2. B 25.6 A
3. C 44.0 A
4. D 39.6 A

### See the step-by-step solution

**Correct choice: A, 22.0 A**

1. General lighting (2026 NEC, 120.41): 2,500 ft² × 2 VA = 5,000 VA.
2. Small-appliance circuits: 2 × 1,500 VA = 3,000 VA. Laundry: 1,500 VA (120.52(A) and (B)).
3. Total before demand: 5,000 + 3,000 + 1,500 = 9,500 VA.
4. First 3,000 VA at 100% = 3,000 VA (Table 120.45).
5. Remaining 6,500 VA × 35% = 2,275 VA.
6. Demand load = 3,000 + 2,275 = 5,275 VA.
7. Watch out: 3 VA per ft² is the old unit load. In the 2026 NEC it is only used to count the general-purpose (lighting and receptacle) branch circuits (120.13), not in this calculation.
8. Current: 5,275 VA ÷ 240 V = 22.0 A (use 240 V for a 120/240 V single-phase service).

## What next?

These 12 questions are fixed. The free diagnostic gives you 12 new questions, shows which topics cost you points and builds a 3-topic plan. For unlimited practice and mock exams of both parts, there is the free week.

Other websites with Texas practice questions, and the NEC edition each one states: [Online practice tests compared (2026 NEC)](https://journeylisto.com/blog/texas-journeyman-practice-tests-compared/).

What about the code part? [Try 10 questions with your book](https://journeylisto.com/texas-journeyman-nec-practice-test/).

## Find your missing points before exam day

12 calculations plus 4 quick questions, about 15–20 minutes, with step-by-step solutions in English or Spanish. No sign-up.

[Take the free diagnostic](https://journeylisto.com/#diagnostic)

Want to practice everything now? [Try 7 days free](https://journeylisto.com/#offer).

Free for 7 days. Then $39 a month until you cancel. We email you 2 days before. Cancel before and you pay nothing.

## Sources

- [PSI: Candidate Information Bulletin, TDLR electricians (updated 9/15/2026), pp. 8 and 12 to 14](https://test-takers.psiexams.com/api/content/bulletin/1682)
- [TDLR: staff report, May 12, 2026 (first-time average on the calculations part)](https://www.tdlr.texas.gov/electricians/agendas/2026-05-12-elc-staff-reports.pdf)
- [NFPA: NFPA 70, National Electrical Code, 2026 edition](https://www.nfpa.org/product/nfpa-70-national-electrical-code-nec/p0070code)

Reviewed October 23, 2026. Published by Brian De Souza, co-founder of JourneyListo. TDLR, PSI and NFPA are the authorities. This is a summary in our own words: check the source before you act on it.

## Start

Free practice test: 12 calculations in about 15–20 minutes, step by step in English or Spanish. No sign-up, and your results right away.

Start the free diagnostic: https://journeylisto.com/start/