# Box fill calculator for the journeyman exam

Source: https://journeylisto.com/box-fill-calculator/ · Updated 2026-10-23

Free calculator · reviewed October 23, 2026

Count **1 for each conductor, 2 for each yoke (device), 1 for all the grounds together (up to 4) and 1 for the internal clamps.** Multiply by each size's volume (NEC 314.16(B)): 14 AWG = 2.00 in³, 12 AWG = 2.25 in³, 10 AWG = 2.50 in³.

## The calculator

Interactive tool on this page: The calculator (https://journeylisto.com/box-fill-calculator/#calculadora)

## Key facts

|  |  |
|---|---|
| Each conductor | 1 allowance at its size (a conductor that only passes through too). |
| Each yoke (device) | 2 allowances, at the largest conductor connected to that device. |
| Equipment grounding conductors | All together, 1 allowance at the largest one (up to 4). Each one over 4 adds ¼. |
| Internal clamps | 1 allowance in all, at the largest conductor in the box. |
| Support fittings | 1 allowance per type (stud or hickey), at the largest conductor. |

Source: NEC 314.16(B), with the volumes per size on this page. Our calculation engine, the same as the diagnostic's, is checked by automated tests.

## Volume per wire size

Volume each conductor takes up, by size (NEC 314.16(B)):

| Size | Volume |
|---|---|
| 18 AWG | 1.50 in³ |
| 16 AWG | 1.75 in³ |
| 14 AWG | 2.00 in³ |
| 12 AWG | 2.25 in³ |
| 10 AWG | 2.50 in³ |
| 8 AWG | 3.00 in³ |
| 6 AWG | 5.00 in³ |

## Worked example

A box with 6 × 12 AWG conductors, 1 receptacle connected to 12 AWG, 2 × 12 AWG grounds and internal clamps.

1. 12 AWG conductors: 6 × 1 = 6. 6 × 2.25 in³ = 13.50 in³.
2. Devices (yokes) with 12 AWG conductors: 1 × 2 = 2. 2 × 2.25 in³ = 4.50 in³.
3. Equipment grounding conductors, 2 in all: all together = 1, at 12 AWG. 1 × 2.25 in³ = 2.25 in³.
4. Internal cable clamps: 1, at the largest conductor (12 AWG). 1 × 2.25 in³ = 2.25 in³.
5. Minimum box volume: 22.50 in³.

## What doesn't count, and other details

- A pigtail that never leaves the box doesn't count.
- An unbroken conductor that passes through counts 1. If it is looped, at least twice the free length the NEC requires for conductors in a box, it counts 2.
- Splicing connectors (wire nuts) don't count.
- On the exam, the question tells you what is in the box. Check for clamps or fittings.
- When conductors are different sizes, each counts at its own volume.

The counting mistakes that cost you points, each with a worked example: [Box fill: the mistakes that cost points](https://journeylisto.com/blog/box-fill-mistakes/).

## 3 practice questions

### Question 1

A box will contain 9 × 12 AWG insulated conductors (all spliced or terminated in the box), 2 switches (each on its own yoke) connected to 12 AWG conductors, and 3 × 12 AWG equipment grounding conductors. There are no internal clamps, fittings or studs. The volume allowance for 12 AWG is 2.25 in³. What is the minimum box volume?

1. A 31.50 in³
2. B 27.00 in³
3. C 29.25 in³
4. D 36.00 in³

### See the step-by-step solution

**Correct choice: A, 31.50 in³**

1. Count allowances (each one = 2.25 in³ for 12 AWG).
2. Insulated conductors: 9 × 1 = 9.
3. 2 devices: 2 × 2 = 4.
4. Equipment grounding conductors, all together: 1.
5. Total: 9 + 4 + 1 = 14 allowances × 2.25 in³ = 31.50 in³.
6. A device yoke counts 2. All the grounds together count just 1 (up to 4 of them).

### Question 2

A box will contain 8 × 14 AWG insulated conductors (all spliced or terminated in the box), 2 switches (each on its own yoke) connected to 14 AWG conductors, and 4 × 14 AWG equipment grounding conductors. There are no internal clamps, fittings or studs. The volume allowance for 14 AWG is 2.00 in³. What is the minimum box volume?

1. A 32.00 in³
2. B 24.00 in³
3. C 22.00 in³
4. D 26.00 in³

### See the step-by-step solution

**Correct choice: D, 26.00 in³**

1. Count allowances (each one = 2.00 in³ for 14 AWG).
2. Insulated conductors: 8 × 1 = 8.
3. 2 devices: 2 × 2 = 4.
4. Equipment grounding conductors, all together: 1.
5. Total: 8 + 4 + 1 = 13 allowances × 2.00 in³ = 26.00 in³.
6. A device yoke counts 2. All the grounds together count just 1 (up to 4 of them).

### Question 3

A box will contain 6 × 12 AWG and 4 × 10 AWG insulated conductors (all spliced or terminated in the box), 1 switch connected to 10 AWG conductors, and these equipment grounding conductors: 2 × 10 AWG and 1 × 12 AWG. There are no internal clamps, fittings or studs. Volume allowances: 12 AWG = 2.25 in³, 10 AWG = 2.50 in³. What is the minimum box volume?

1. A 35.75 in³
2. B 31.00 in³
3. C 28.50 in³
4. D 32.50 in³

### See the step-by-step solution

**Correct choice: B, 31.00 in³**

1. 12 AWG conductors: 6 × 2.25 = 13.50 in³.
2. 10 AWG conductors: 4 × 2.50 = 10.00 in³.
3. Device: 2 × 2.50 in³ (based on the largest conductor connected to it, 10 AWG) = 5.00 in³.
4. Equipment grounding conductors: one allowance for the largest one (10 AWG) = 2.50 in³.
5. Minimum volume: 13.50 + 10.00 + 5.00 + 2.50 = 31.00 in³.

## Find your missing points before exam day

12 calculations plus 4 quick questions, about 15–20 minutes, with step-by-step solutions in English or Spanish. No sign-up.

[Take the free diagnostic](https://journeylisto.com/#diagnostic)

Want to practice everything now? [Try 7 days free](https://journeylisto.com/#offer).

Free for 7 days. Then $39 a month until you cancel. We email you 2 days before. Cancel before and you pay nothing.

## Sources

- [NFPA: NFPA 70, National Electrical Code, 2026 edition (314.16(B))](https://www.nfpa.org/product/nfpa-70-national-electrical-code-nec/p0070code)
- [PSI: Candidate Information Bulletin (updated 9/15/2026), p. 14 (boxes on the calculations portion)](https://test-takers.psiexams.com/api/content/bulletin/1682)

Reviewed October 23, 2026. Published by Brian De Souza, co-founder of JourneyListo. TDLR, PSI and NFPA are the authorities. This is a summary in our own words: check the source before you act on it.

## Start

Free practice test: 12 calculations in about 15–20 minutes, step by step in English or Spanish. No sign-up, and your results right away.

Start the free diagnostic: https://journeylisto.com/start/