# Voltage drop on the journeyman exam: worked problems, step by step

Source: https://journeylisto.com/blog/voltage-drop-practice-problems/ · Updated 2026-10-26

Blog · reviewed October 26, 2026

**One formula solves all 4 kinds of voltage drop problem below: VD = 2 × K × I × L ÷ CM for single-phase, with 1.732 in place of the 2 for three-phase.** It gives you the volts and the percent; solved the other way, the minimum wire size and the maximum length. Here are 4 worked problems, with K = 12.9 for copper and the circular mils from Chapter 9, Table 8.

## Key facts

|  |  |
|---|---|
| Single-phase | VD = 2 × K × I × L ÷ CM |
| Three-phase | VD = 1.732 × K × I × L ÷ CM |
| Percent | VD ÷ source voltage × 100 |
| Minimum size | CM = 2 × K × I × L ÷ allowed VD (1.732 for three-phase). Then the first Table 8 size with at least that many CM. |
| Maximum length | L = allowed VD × CM ÷ (2 × K × I) (1.732 for three-phase). Round down. |
| K and L | K = 12.9 for copper and 21.2 for aluminum (at 75 °C). L is the one-way length in feet. |
| On the exam | Conductors are copper unless the question says otherwise. |

Source: [IAEI, Voltage Drop Calculations](https://iaeimagazine.org/electrical-fundamentals/voltage-drop-calculations/) (the formulas and K), [NFPA](https://www.nfpa.org/product/nfpa-70-national-electrical-code-nec/p0070code) (Chapter 9, Table 8), the [PSI bulletin](https://test-takers.psiexams.com/api/content/bulletin/1682), p. 13 (copper), and our calculation engine, the same as the calculator's, checked by automated tests.

## Problem 1: single-phase, the drop in volts

A 240 V single-phase circuit uses 8 AWG copper conductors. It carries 30 A to a load 160 ft away (one-way length). Using K = 12.9, what is the voltage drop in volts? (Find the table values you need in your own 2026 NEC.)

1. Chapter 9, Table 8: 8 AWG = 16,510 circular mils.
2. Single-phase voltage drop: VD = 2 × K × I × L ÷ CM.
3. VD = 2 × 12.9 × 30 × 160 ÷ 16,510 = 123,840 ÷ 16,510 = 7.50 V.
4. The 2 already counts both conductors (out and back), so use the one-way length and do not double it again.

**Answer: 7.50 V** (3.13% of 240 V).

Check it in the [calculator](https://journeylisto.com/voltage-drop-calculator/#calculadora): single-phase, copper, 8 AWG, 30 A, 160 ft, 240 V.

## Problem 2: three-phase, the percent

A 208 V three-phase circuit uses 1/0 AWG copper conductors. It carries 100 A to a load 200 ft away (one-way length). Using K = 12.9 and 1.732 for √3, what percent of the 208 V source voltage is lost to voltage drop? (Find the table values you need in your own 2026 NEC.)

1. Chapter 9, Table 8: 1/0 AWG = 105,600 circular mils.
2. Three-phase voltage drop: VD = 1.732 × K × I × L ÷ CM.
3. VD = 1.732 × 12.9 × 100 × 200 ÷ 105,600 = 446,856 ÷ 105,600 = 4.232 V.
4. Percent = 4.232 V ÷ 208 V × 100 = 2.03%.
5. Three-phase uses 1.732 (√3) in place of the single-phase 2.
6. Small rounding differences are normal; pick the closest choice.

**Answer: 2.03%** (4.23 V of 208 V).

Check it in the [calculator](https://journeylisto.com/voltage-drop-calculator/#calculadora): three-phase, copper, 1/0 AWG, 100 A, 200 ft, 208 V.

## Problem 3: the minimum wire size

A 120 V single-phase circuit carries 20 A to a load 120 ft away (one-way length). Copper conductors, K = 12.9. The voltage drop can't be more than 3%. What is the smallest wire size that works?

1. Allowed drop: 3% of 120 V = 0.03 × 120 = 3.6 V.
2. Solve for CM: CM = 2 × K × I × L ÷ VD = 2 × 12.9 × 20 × 120 ÷ 3.6 = 61,920 ÷ 3.6 = 17,200 CM.
3. In Chapter 9, Table 8, the first size with 17,200 CM or more is 6 AWG (26,240 CM). 8 AWG has 16,510 CM: not enough.
4. Check it: with 6 AWG, VD = 61,920 ÷ 26,240 = 2.36 V (1.97%). With 8 AWG it would be 3.75 V (3.13%), over 3.6 V.

**Answer: 6 AWG.** When you pick the size, never round down: if the CM fall short, the drop goes over the limit.

Check it in the [calculator](https://journeylisto.com/voltage-drop-calculator/#calculadora): single-phase, copper, 6 AWG, 20 A, 120 ft, 120 V. Then switch to 8 AWG.

## Problem 4: the maximum length

A 208 V three-phase circuit with 6 AWG copper conductors carries 40 A. Using K = 12.9 and 1.732 for √3, with a voltage drop that can't be more than 3%, how far away (one-way) can the load be?

1. Allowed drop: 3% of 208 V = 0.03 × 208 = 6.24 V.
2. Chapter 9, Table 8: 6 AWG = 26,240 circular mils.
3. Solve for L: L = VD × CM ÷ (1.732 × K × I).
4. L = 6.24 × 26,240 ÷ (1.732 × 12.9 × 40) = 163,737.6 ÷ 893.712 = 183.21 ft.
5. Round down: 183 ft. At 183 ft, VD = 6.23 V; at 184 ft it would be 6.27 V, over 6.24 V.

**Answer: 183 ft.** For a maximum length, round down: if you round up, the drop goes over the limit.

Check it in the [calculator](https://journeylisto.com/voltage-drop-calculator/#calculadora): three-phase, copper, 6 AWG, 40 A, 183 ft, 208 V.

## Common mistakes (and what they give)

In problem 1:

- Forgetting the 2: gives 3.75 V.
- Reading the circular mils from the next row of Table 8 (6 AWG instead of 8 AWG): gives 4.72 V.
- Using 1.732 on a single-phase circuit: gives 6.50 V.
- Doubling the length (320 ft): gives 15.00 V. The 2 already counts out and back.

In problem 2:

- Using 2 on a three-phase circuit: gives 2.35%.
- Reading the circular mils from the next row of Table 8 (2/0 AWG instead of 1/0 AWG): gives 1.61%.
- Leaving out the 1.732: gives 1.17%.

## On the exam

- Check whether it asks for volts or for a percent of the source voltage.
- Use the one-way length, source to load: the 2 (or the 1.732) does the rest. If a question gives the total conductor length (out and back), use half of it.
- Conductors are copper unless the question says otherwise. If the question gives K or the circular mils, use those.
- If the question gives a voltage-drop limit (for example, 3%), that's the one you use.
- On the calculations part you have 110 minutes for 26 questions: about 4.2 minutes per question.

All the formulas on one page: [the exam formula sheet](https://journeylisto.com/journeyman-formula-sheet/). How to learn them: [how to memorize the formulas](https://journeylisto.com/blog/how-to-memorize-journeyman-exam-formulas/).

## Try it with your own numbers

The voltage drop calculator gives you the drop, the percent and the steps, single-phase or three-phase. Under the result you can ask us to email it to you, steps included.

[Open the calculator](https://journeylisto.com/voltage-drop-calculator/#calculadora)

## What about the other calculation topics?

12 calculations plus 4 quick questions, about 15–20 minutes, with step-by-step solutions in English or Spanish. No sign-up.

[Take the free diagnostic](https://journeylisto.com/#diagnostic)

Want to practice everything now? [Try 7 days free](https://journeylisto.com/#offer).

Free for 7 days. Then $39 a month until you cancel. We email you 2 days before. Cancel before and you pay nothing.

## Sources

- [IAEI: Voltage Drop Calculations (VD, CM and maximum length; K = 12.9 copper, 21.2 aluminum, from Table 8 at 75 °C)](https://iaeimagazine.org/electrical-fundamentals/voltage-drop-calculations/)
- [NFPA: NFPA 70, National Electrical Code, 2026 edition (Chapter 9, Table 8)](https://www.nfpa.org/product/nfpa-70-national-electrical-code-nec/p0070code)
- [PSI: Candidate Information Bulletin (updated 9/15/2026), pp. 13 and 14 (26 questions in 110 minutes; copper unless stated)](https://test-takers.psiexams.com/api/content/bulletin/1682)

Reviewed October 26, 2026. Published by Brian De Souza, co-founder of JourneyListo. TDLR, PSI and NFPA are the authorities. This is a summary in our own words: check the source before you act on it.

## Start

Free practice test: 12 calculations in about 15–20 minutes, step by step in English or Spanish. No sign-up, and your results right away.

Start the free diagnostic: https://journeylisto.com/start/