# Dwelling load calculation with the 2026 NEC (Article 120), step by step

Source: https://journeylisto.com/blog/dwelling-load-calculation-2026-nec/ · Updated 2026-10-23

Blog · reviewed October 23, 2026

**2026 NEC standard method: general lighting per square foot, plus 1,500 VA for each small-appliance and laundry circuit, then the Table 120.45 demand factors on the total.** For a 2,000 ft² house at 2 VA per square foot, with 2 small-appliance circuits and 1 laundry circuit: 4,000 + 4,500 = 8,500 VA; the first 3,000 VA at 100% and the other 5,500 VA at 35% come to 4,925 VA. The house's other loads, such as the range and the dryer, are added after that. In the 2023 NEC it was 3 VA per square foot: in the 2026 NEC that value only counts branch circuits (120.13).

## Key facts

|  |  |
|---|---|
| Where it is | 2026 NEC Article 120 (Article 220 in the 2023 NEC). |
| General lighting | 2 VA per ft² (120.41). It was 3 VA in the 2023 NEC. |
| Small-appliance circuits | 1,500 VA per circuit (120.52(A)). |
| Laundry | 1,500 VA per circuit (120.52(B)). |
| Demand factors | Table 120.45: first 3,000 VA at 100%, 3,001 to 120,000 VA at 35% and the rest at 25%. |
| 3 VA per ft² | In the 2026 NEC it counts branch circuits (120.13); it isn't used in this calculation. |

Source: NFPA ([tables of contents](https://www.nfpa.org/product/nfpa-70-national-electrical-code-nec/p0070code), [2026 NEC Handbook, 120.52 to 120.54](https://docinfofiles.nfpa.org/files/AboutTheCodes/70/Errata_NEC_Handbook_2026_Table_120.54.pdf), [Standards Council minutes, 120.13](https://content.nfpa.org/-/media/Project/Storefront/Catalog/Files/Codes-and-standards/standards-council/August-2025/SC_Final_Minutes_08_2025.pdf?rev=-1&hash=F9A19D2F22F36C15D16A26B45762A00C), [Code-Making Panel 2 working drafts](https://docinfofiles.nfpa.org/files/AboutTheCodes/70/70_A2025_NEC_P02_FD_PrelimFR.pdf), 120.41 and Annex D), [EC&M](https://www.ecmweb.com/national-electrical-code/article/55371139/changes-to-dwelling-unit-calculations-in-the-2026-nec) and our calculation engine, checked by automated tests.

**2 VA per ft² (120.41), not 3.** We checked it in NFPA's working drafts of Code-Making Panel 2's meetings for the 2026 NEC: in the January 2024 one, [First Revision FR-8013](https://docinfofiles.nfpa.org/files/AboutTheCodes/70/70_A2025_NEC_P02_FD_PrelimFR.pdf) changes 3 to 2 VA; in the October 2024 one, the Annex D dwelling example ([SR-7950](https://docinfofiles.nfpa.org/files/AboutTheCodes/70/70_A2025_NEC_P02_SD_PrelimSR.pdf)) figures 1,500 ft² at 2 VA = 3,000 VA, with the first 3,000 VA at 100% and the other 4,500 VA at 35%. No [2025 Technical Meeting motion](https://docinfofiles.nfpa.org/files/AboutTheCodes/70/NITMAM_MC_Report_A2025.pdf) changed 120.41, and guides such as [EC&M](https://www.ecmweb.com/national-electrical-code/article/55371139/changes-to-dwelling-unit-calculations-in-the-2026-nec) also give 2 VA. Those drafts don't change Table 120.45. We didn't read the printed text (NFPA asks for an account to read it free online): find it in your book.

## Step by step: a 2,000 ft² house

Standard method (2026 NEC), single-family dwelling of 2,000 ft². Find the demand load for general lighting plus the 2 small-appliance circuits and 1 laundry circuit. Use 2 VA per ft², 1,500 VA per circuit, and these demand factors: first 3,000 VA at 100%, the rest (up to 120,000 VA) at 35%.

1. General lighting (2026 NEC, 120.41): 2,000 ft² × 2 VA = 4,000 VA.
2. Small-appliance circuits: 2 × 1,500 VA = 3,000 VA. Laundry: 1,500 VA (120.52(A) and (B)).
3. Total before demand: 4,000 + 3,000 + 1,500 = 8,500 VA.
4. First 3,000 VA at 100% = 3,000 VA (Table 120.45).
5. Remaining 5,500 VA × 35% = 1,925 VA.
6. Demand load = 3,000 + 1,925 = 4,925 VA.
7. Watch out: 3 VA per ft² is the old unit load. In the 2026 NEC it is only used to count the general-purpose (lighting and receptacle) branch circuits (120.13), not in this calculation.
8. Add the small-appliance and laundry loads before applying the demand factors.

**Result: 4,925 VA.**

## In amperes

Current: 4,925 VA ÷ 240 V = 20.5 A (use 240 V for a 120/240 V single-phase service).

## Common mistakes (and what they give)

In the 2,000 ft² example:

- Leaving out the small-appliance and laundry circuits: gives 3,350 VA.
- Using 3 VA per ft² (the old unit load): gives 5,625 VA.
- Skipping the demand factors: gives 8,500 VA.
- Dividing by 120 V instead of 240 V: gives 41.0 A.

## On the exam

On the calculations part, PSI's bulletin puts load calculations under services (4 questions) and feeders (3 questions) ([PSI bulletin](https://test-takers.psiexams.com/api/content/bulletin/1682), pp. 13 and 14). Per TDLR, the first-time average was 2.08 of 4 on services and 1.45 of 3 on feeders ([TDLR staff report, May 12, 2026](https://www.tdlr.texas.gov/electricians/agendas/2026-05-12-elc-staff-reports.pdf)).

The bulletin also says not to use optional calculation methods unless the question asks: that's why this is the standard method.

## What comes next in a full house

The full calculation adds more loads. Two 2026 NEC rules we checked on an NFPA 2026 NEC Handbook page:

- **120.53:** a 75% demand factor is permitted for four or more fastened-in-place appliances, each rated ¼ hp or 500 W or more, on the same feeder or service. It doesn't apply to fixed electric cooking equipment, dryers, space heating, air conditioning or EV chargers (EVSE).
- **120.54:** each dryer counts at 5,000 W or its nameplate rating, whichever is larger.

For ranges, air conditioning and heating, check your book: we don't print those values here.

To print: [the 2023 to 2026 NEC changes sheet](https://journeylisto.com/2023-to-2026-nec-changes-sheet/), with 5 questions.

## 2 practice questions

### Question 1

Standard method (2026 NEC), single-family dwelling of 1,700 ft². Find the demand load for general lighting plus the 2 small-appliance circuits and 1 laundry circuit. Use 2 VA per ft², 1,500 VA per circuit, and these demand factors: first 3,000 VA at 100%, the rest (up to 120,000 VA) at 35%.

1. A 3,140 VA
2. B 5,310 VA
3. C 4,715 VA
4. D 7,900 VA

### See the step-by-step solution

**Correct choice: C, 4,715 VA**

1. General lighting (2026 NEC, 120.41): 1,700 ft² × 2 VA = 3,400 VA.
2. Small-appliance circuits: 2 × 1,500 VA = 3,000 VA. Laundry: 1,500 VA (120.52(A) and (B)).
3. Total before demand: 3,400 + 3,000 + 1,500 = 7,900 VA.
4. First 3,000 VA at 100% = 3,000 VA (Table 120.45).
5. Remaining 4,900 VA × 35% = 1,715 VA.
6. Demand load = 3,000 + 1,715 = 4,715 VA.
7. Watch out: 3 VA per ft² is the old unit load. In the 2026 NEC it is only used to count the general-purpose (lighting and receptacle) branch circuits (120.13), not in this calculation.
8. Add the small-appliance and laundry loads before applying the demand factors.

### Question 2

A 2,700 ft² single-family dwelling, standard method (2026 NEC): general lighting at 2 VA per ft² plus 2 small-appliance circuits and 1 laundry circuit at 1,500 VA each, with demand factors applied (first 3,000 VA at 100%, the rest at 35%). What is that demand load in amperes on a 120/240 V single-phase service?

1. A 26.5 A
2. B 41.3 A
3. C 45.1 A
4. D 22.6 A

### See the step-by-step solution

**Correct choice: D, 22.6 A**

1. General lighting (2026 NEC, 120.41): 2,700 ft² × 2 VA = 5,400 VA.
2. Small-appliance circuits: 2 × 1,500 VA = 3,000 VA. Laundry: 1,500 VA (120.52(A) and (B)).
3. Total before demand: 5,400 + 3,000 + 1,500 = 9,900 VA.
4. First 3,000 VA at 100% = 3,000 VA (Table 120.45).
5. Remaining 6,900 VA × 35% = 2,415 VA.
6. Demand load = 3,000 + 2,415 = 5,415 VA.
7. Watch out: 3 VA per ft² is the old unit load. In the 2026 NEC it is only used to count the general-purpose (lighting and receptacle) branch circuits (120.13), not in this calculation.
8. Current: 5,415 VA ÷ 240 V = 22.6 A (use 240 V for a 120/240 V single-phase service).

## Practice dwelling loads

The free week includes calculation practice (12 topics), with step-by-step solutions.

[Try 7 days free](https://journeylisto.com/#offer)

Free for 7 days. Then $39 a month until you cancel. We email you 2 days before. Cancel before and you pay nothing.

Rather start without a card? Take the [free diagnostic](https://journeylisto.com/#diagnostic).

## Sources

- [NFPA: NFPA 70 catalog (2023 and 2026 tables of contents: Article 220 → 120)](https://www.nfpa.org/product/nfpa-70-national-electrical-code-nec/p0070code)
- [NFPA: 2026 NEC Handbook, errata replacement page (120.52 to 120.54)](https://docinfofiles.nfpa.org/files/AboutTheCodes/70/Errata_NEC_Handbook_2026_Table_120.54.pdf)
- [NFPA: Standards Council minutes, August 2025 (120.13)](https://content.nfpa.org/-/media/Project/Storefront/Catalog/Files/Codes-and-standards/standards-council/August-2025/SC_Final_Minutes_08_2025.pdf?rev=-1&hash=F9A19D2F22F36C15D16A26B45762A00C)
- [NFPA: working draft of Code-Making Panel 2's First Draft meeting, January 2024 (FR-8013: 120.41, 3 to 2 VA per square foot)](https://docinfofiles.nfpa.org/files/AboutTheCodes/70/70_A2025_NEC_P02_FD_PrelimFR.pdf)
- [NFPA: working draft of Code-Making Panel 2's Second Draft meeting, October 2024 (SR-7950: Annex D dwelling example at 2 VA per square foot)](https://docinfofiles.nfpa.org/files/AboutTheCodes/70/70_A2025_NEC_P02_SD_PrelimSR.pdf)
- [NFPA: Motions Committee report for the 2025 Technical Meeting (the only Article 120 motion was on 120.13)](https://docinfofiles.nfpa.org/files/AboutTheCodes/70/NITMAM_MC_Report_A2025.pdf)
- [EC&M: Changes to Dwelling Unit Calculations in the 2026 NEC (120.41)](https://www.ecmweb.com/national-electrical-code/article/55371139/changes-to-dwelling-unit-calculations-in-the-2026-nec)
- [PSI: Candidate Information Bulletin (updated 9/15/2026), pp. 8, 13 and 14](https://test-takers.psiexams.com/api/content/bulletin/1682)
- [TDLR: staff report, May 12, 2026 (topic averages)](https://www.tdlr.texas.gov/electricians/agendas/2026-05-12-elc-staff-reports.pdf)

Reviewed October 23, 2026. Published by Brian De Souza, co-founder of JourneyListo. TDLR, PSI and NFPA are the authorities. This is a summary in our own words: check the source before you act on it.