# Box fill (NEC 314.16): the counting mistakes that cost you points

Source: https://journeylisto.com/blog/box-fill-mistakes/ · Updated 2026-10-26

Blog · reviewed October 26, 2026

**In box fill (NEC 314.16(B)), the main things you count each have a fixed number of allowances: 1 per conductor, 2 per yoke (device), 1 for all the equipment grounding conductors together (up to 4), 1 for the internal clamps and 1 for each type of support fitting.** Miscount one thing and the volume comes out wrong. Here are 6 counting mistakes, each with a worked example and what it gives.

## Key facts

|  |  |
|---|---|
| Each conductor | 1 allowance at its size (a conductor that only passes through too). |
| Each device (yoke) | 2 allowances, at the largest conductor connected to that device. |
| Equipment grounding conductors | All together, 1 allowance at the largest one (up to 4). Each one over 4 adds ¼. |
| Internal clamps | 1 allowance in all, at the largest conductor in the box. |
| Support fittings | 1 allowance per type (stud or hickey), at the largest conductor. |
| Volume per conductor | 14 AWG = 2.00 in³, 12 AWG = 2.25 in³, 10 AWG = 2.50 in³. |

Source: NEC 314.16(B), with the volumes and rules of our box fill calculator; the [PSI bulletin](https://test-takers.psiexams.com/api/content/bulletin/1682), p. 14 (boxes on the calculations part). Our calculation engine is checked by automated tests.

Exam coming up? [Practice both parts of the Texas journeyman exam](https://journeylisto.com/).

## Mistake 1: counting the device as 1

A box has 4 × 14 AWG conductors, 1 switch connected to them and 2 × 14 AWG equipment grounding conductors (EGCs). No clamps or fittings.

1. 14 AWG conductors: 4 × 1 = 4. 4 × 2.00 in³ = 8.00 in³.
2. Devices (yokes) with 14 AWG conductors: 1 × 2 = 2. 2 × 2.00 in³ = 4.00 in³.
3. Equipment grounding conductors, 2 in all: all together = 1, at 14 AWG. 1 × 2.00 in³ = 2.00 in³.
4. Minimum box volume: 14.00 in³.

**Right: 14.00 in³.** Each yoke (the device's metal strap) counts 2, at the size of the largest conductor connected to that device. A duplex receptacle is on one yoke: it counts 2.

- Counting the switch as 1 gives 6 allowances: 12.00 in³, a box smaller than needed.

## Mistake 2: counting each ground

A box has 6 × 12 AWG conductors, 1 receptacle connected to them and 3 × 12 AWG EGCs (for example, three 12/2 NM cables with ground).

1. 12 AWG conductors: 6 × 1 = 6. 6 × 2.25 in³ = 13.50 in³.
2. Devices (yokes) with 12 AWG conductors: 1 × 2 = 2. 2 × 2.25 in³ = 4.50 in³.
3. Equipment grounding conductors, 3 in all: all together = 1, at 12 AWG. 1 × 2.25 in³ = 2.25 in³.
4. Minimum box volume: 20.25 in³.

**Right: 20.25 in³.** All the equipment grounding conductors together count 1, at the size of the largest one, up to 4.

- Counting the 3 grounds as 3 gives 11 allowances: 24.75 in³.

## Mistake 3: more than 4 grounds

A two-device box has 12 × 12 AWG conductors, 2 receptacles connected to them and 6 × 12 AWG EGCs.

1. 12 AWG conductors: 12 × 1 = 12. 12 × 2.25 in³ = 27.00 in³.
2. Devices (yokes) with 12 AWG conductors: 2 × 2 = 4. 4 × 2.25 in³ = 9.00 in³.
3. Equipment grounding conductors, 6 in all: 1 for the first 4 + 2 × ¼ = 1.5, at 12 AWG. 1.5 × 2.25 in³ = 3.375 in³.
4. Minimum box volume: 39.375 in³.

**Right: 39.375 in³.** The first 4 grounds count 1. Each ground over 4 adds ¼.

- Counting the 6 grounds as 1, without the ¼ for each extra one, gives 17 allowances: 38.25 in³, a box smaller than needed.

## Mistake 4: mixed wire sizes

A box has 4 × 14 AWG and 2 × 12 AWG conductors, 1 switch connected only to 14 AWG conductors, and 2 EGCs: one 12 AWG and one 14 AWG.

1. 14 AWG conductors: 4 × 1 = 4. 4 × 2.00 in³ = 8.00 in³.
2. 12 AWG conductors: 2 × 1 = 2. 2 × 2.25 in³ = 4.50 in³.
3. Devices (yokes) with 14 AWG conductors: 1 × 2 = 2. 2 × 2.00 in³ = 4.00 in³.
4. Equipment grounding conductors, 2 in all: all together = 1, at 12 AWG. 1 × 2.25 in³ = 2.25 in³.
5. Minimum box volume: 18.75 in³.

**Right: 18.75 in³.** Each conductor counts at its own size. The device, at the largest conductor connected to it. The grounds, at the size of the largest ground.

- Putting the switch at the box's largest size (12 AWG) gives 19.25 in³. It goes at the size of its own conductors (14 AWG).
- Putting the grounds at the smaller one's size (14 AWG) gives 18.50 in³, a box smaller than needed.
- Counting everything as 12 AWG gives 9 × 2.25 in³ = 20.25 in³.

## Mistake 5: internal clamps

The box from mistake 1 (4 × 14 AWG conductors, 1 switch and 2 × 14 AWG EGCs), now with 2 internal cable clamps.

1. 14 AWG conductors: 4 × 1 = 4. 4 × 2.00 in³ = 8.00 in³.
2. Devices (yokes) with 14 AWG conductors: 1 × 2 = 2. 2 × 2.00 in³ = 4.00 in³.
3. Equipment grounding conductors, 2 in all: all together = 1, at 14 AWG. 1 × 2.00 in³ = 2.00 in³.
4. Internal cable clamps: 1, at the largest conductor (14 AWG). 1 × 2.00 in³ = 2.00 in³.
5. Minimum box volume: 16.00 in³.

**Right: 16.00 in³.** All the internal clamps together count 1, at the largest conductor in the box.

- Forgetting the clamps gives 14.00 in³, a box smaller than needed.
- Counting each clamp (2) gives 18.00 in³.

## Mistake 6: support fittings

A ceiling box for a luminaire has 4 × 14 AWG conductors, 2 × 14 AWG EGCs, a fixture stud and a hickey. No devices or clamps.

1. 14 AWG conductors: 4 × 1 = 4. 4 × 2.00 in³ = 8.00 in³.
2. Equipment grounding conductors, 2 in all: all together = 1, at 14 AWG. 1 × 2.00 in³ = 2.00 in³.
3. Support fittings (studs or hickeys): 2 × 1, at the largest conductor (14 AWG). 2 × 2.00 in³ = 4.00 in³.
4. Minimum box volume: 14.00 in³.

**Right: 14.00 in³.** Each type of support fitting (a stud, a hickey) counts 1, at the largest conductor in the box.

- Forgetting the stud and the hickey gives 10.00 in³, a box smaller than needed.
- Counting the stud and the hickey together as 1 gives 12.00 in³, a box smaller than needed.

## What doesn't count

- A pigtail that never leaves the box doesn't count.
- Splicing connectors (wire nuts) don't count.
- An unbroken conductor that passes through counts 1. If it is looped, at least twice the free length the NEC requires for conductors in a box, it counts 2.

## On the exam

On the calculations part, PSI's bulletin puts boxes and enclosures under wiring methods and materials, together with raceways: a topic with 2 scored questions. On the NEC knowledge part they are in the same topic, which has 10 there.

- The question tells you what is in the box. Check for clamps or fittings.
- Count first, multiply second: write down how many allowances go at each size.
- If it asks you to pick a box, pick one with at least that volume.

The counting rules on one page: [the exam formula sheet](https://journeylisto.com/journeyman-formula-sheet/). EGC, enclosure, raceway: what they are in Spanish, in [NEC terms Spanish speakers mix up](https://journeylisto.com/blog/nec-terms-spanish-speakers-mix-up/).

## Count your box in the calculator

The box fill calculator adds up the allowances at each size, with grounds, clamps and fittings, and shows the steps. Under the result you can ask us to email it to you.

[Open the calculator](https://journeylisto.com/box-fill-calculator/#calculadora)

## What about the other calculation topics?

12 calculations plus 4 quick questions, about 15–20 minutes, with step-by-step solutions in English or Spanish. No sign-up.

[Take the free diagnostic](https://journeylisto.com/#diagnostic)

Want to practice everything now? [Try 7 days free](https://journeylisto.com/#offer).

Free for 7 days. Then $39 a month until you cancel. We email you 2 days before. Cancel before and you pay nothing.

## Sources

- [NFPA: NFPA 70, National Electrical Code, 2026 edition (314.16(B))](https://www.nfpa.org/product/nfpa-70-national-electrical-code-nec/p0070code)
- [PSI: Candidate Information Bulletin (updated 9/15/2026), pp. 12 and 14 (boxes and enclosures on both parts)](https://test-takers.psiexams.com/api/content/bulletin/1682)

Reviewed October 26, 2026. Published by Brian De Souza, co-founder of JourneyListo. TDLR, PSI and NFPA are the authorities. This is a summary in our own words: check the source before you act on it.